Wire Size & Voltage Drop Calculator

Calculate wire size and voltage drop using NEC 310.16 and IEC 60364 dual-constraint sizing engine. Snaps to commercial metric mm² and AWG with distance-to-failure simulation.

Construction Calculators

Electrical System Parameters

Conductor Material
Maximum Allowable Voltage Drop
Circuit System
Nominal Supply Voltage
Equivalent:147.6 ft
Dual-Constraint Sizing Engine Results
Governed by Voltage Drop Limit (Efficiency & Code)
Thermal Ampacity MinNEC 310.16
4 mm²
10 AWG
Ampacity: 34 A (Load: 32 A)
Voltage Drop (3%) Min3%
10 mm²
8 AWG
Theoretical Area: 7.30 mm²
Final Recommended Conductor SizeVDROP DOMINANT
10 mm²
8 AWG
European Metric Standard & North American AWG Standard100% PASS
Passes Lighting / Critical Code (≤ 3%)
10 mm² (6 AWG) • 5.04 V (2.19%)
Terminal Voltage (Load)225.0 V

Real-Time Circuit Telemetry

Simulated: 10 mm² (6 AWG) • 61A (continuous at 75°C)
Voltage Drop (Vd)5.04 V
Percentage Drop (%)2.19%
Terminal Voltage (Load)225.0 V
Total Loop Resistance0.1575 Ω
Conductor Heat Dissipation161.3 W
Thermal Headroom47.5%

Distance-to-Failure Interactive Slider

Drag the slider to test longer distances. Observe when the circuit violates code thresholds.

Voltage Drop at Current Distance:2.19% (5.0V)
1 m45 Meters (m)150 m
Max Distance for 3% Drop:61.6 m
Max Distance for 5% Drop:102.7 m
Dual-Constraint Sizing Engine (NEC 310.16 & IEC 60364)
10 mm² (8 AWG) • 5.04 V (2.19%)

Commercial Conductor Sizing Matrix & Simulation

Click any row in the matrix below to simulate circuit performance with that specific cable gauge.

Commercial SizeDrop (V)Drop (%)Load VoltageHeat LossAmpacity (75°C)Status
1.5 mm²
33.60 V14.61%196.4 V1075 W16 AOVERHEATING / FIRE RISK
2.5 mm²
20.16 V8.77%209.8 V645 W25 AOVERHEATING / FIRE RISK
4 mm²
12.60 V5.48%217.4 V403 W34 AVOLTAGE DROP FAIL
6 mm²
8.40 V3.65%221.6 V269 W44 AVOLTAGE DROP FAIL
10 mm²REC
5.04 V2.19%225.0 V161 W61 ARECOMMENDED
16 mm²
3.15 V1.37%226.8 V101 W82 APASS
25 mm²
2.02 V0.88%228.0 V65 W108 APASS
35 mm²
1.44 V0.63%228.6 V46 W135 APASS
50 mm²
1.01 V0.44%229.0 V32 W168 APASS
70 mm²
0.72 V0.31%229.3 V23 W213 APASS
95 mm²
0.53 V0.23%229.5 V17 W258 APASS
120 mm²
0.42 V0.18%229.6 V13 W299 APASS
150 mm²
0.34 V0.15%229.7 V11 W344 APASS
185 mm²
0.27 V0.12%229.7 V9 W392 APASS
240 mm²
0.21 V0.09%229.8 V7 W461 APASS
300 mm²
0.17 V0.07%229.8 V5 W530 APASS
400 mm²
0.13 V0.05%229.9 V4 W620 APASS
Wire Sizing & Voltage Drop Equations (NEC / IEC Standards)
DC & 1-Phase (1Φ): Vdrop = 2 × L × I × ρA
3-Phase (3Φ): Vdrop = √3 × L × I × ρA
Min Conductor Area: Amin = k × L × I × ρVsource × (%Vdrop / 100)

Variables:

  • L: One-way circuit run distance in meters (factor 2 accounts for return conductor)
  • I: Load current in Amperes (A)
  • ρ: Conductor electrical resistivity at 20°C (Copper = 0.0175 Ω·mm²/m; Aluminum = 0.0282 Ω·mm²/m)
  • A: Conductor cross-sectional area in mm²
  • k: Phase coefficient (2 for DC & Single-Phase; √3 ≈ 1.732 for Three-Phase)
  • Vdrop: Voltage drop in Volts (V) or percentage (%Vdrop)

What is Wire Size & Voltage Drop Calculator?

Calculate wire size and voltage drop using NEC 310.16 and IEC 60364 dual-constraint sizing engine. Snaps to commercial metric mm² and AWG with distance-to-failure simulation. This platform eliminates the risk of electrical fires and equipment malfunction by evaluating both thermal ampacity and voltage drop simultaneously. The Dual-Constraint Sizing Engine Results panel definitively highlights which factor is dictating the wire size, ensuring your circuits remain safe under continuous load. The Real-Time Circuit Telemetry offers a live readout of terminal voltage and heat dissipation.

Practical Calculation Example

A commercial solar contractor in Arizona is wiring a heavy-duty inverter to a main breaker panel located 45 meters away. They input the 32A design load and a 230V single-phase supply. The system's dual-constraint engine determines that while a 4 mm² (12 AWG) wire can handle the heat, the distance requires a massive jump to a 10 mm² (8 AWG) conductor to keep the voltage drop under the critical 3% limit. To plan for future expansion, the contractor drags the Distance-to-Failure Interactive Slider to see exactly at what meter mark the 8 AWG wire will fail code, before hitting Copy Electrician BOM Spec to order the copper.

Conductor Ampacity & Commercial Reference Table (75°C Copper & Aluminum)

Metric Size (mm²) North American AWG Copper Ampacity (75°C) Aluminum Ampacity (75°C) Max 3% Distance @ Rated Load (230V)
1.5 mm² 14 AWG (2.08 mm²) 16 A Not Permitted (<2.5) 18.5 m (60.7 ft)
2.5 mm² 12 AWG (3.31 mm²) 25 A 18.5 A 24.6 m (80.7 ft)
4.0 mm² 10 AWG (5.26 mm²) 34 A 25 A 28.9 m (94.8 ft)
6.0 mm² 8 AWG (8.37 mm²) 44 A 32 A 33.5 m (109.9 ft)
10.0 mm² 6 AWG (13.3 mm²) 61 A 46 A 40.3 m (132.2 ft)
16.0 mm² 4 AWG (21.2 mm²) 82 A 62 A 48.0 m (157.5 ft)
25.0 mm² 2 AWG (33.6 mm²) 108 A 83 A 56.9 m (186.7 ft)

History and Origin

The American Wire Gauge (AWG) system was created in 1857 by J.R. Brown to standardize the chaotic wire manufacturing industry. Before this, every foundry had its own proprietary sizing. By creating a logarithmic mathematical progression based on the wire drawing process, AWG allowed electrical engineers designing the early telegraph networks to accurately calculate resistance and voltage drop over vast distances.